看真人视频一级毛片免费观看,免费观看一级二级黄色视频免费观看,久久www免费人成看片老司机,毛片一级a一区二区在线,国产一级黄片AAA免费看,午夜一级毛片在线,欧美一级A视频免费观看,国产a毛一级a视频,久热香蕉在线视频免费版

Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
CN EN

Vacuum interrupter for contactor TJ040K

Model:VITJ1.14/1250-10

Category:VI for contactors

Product details

1435904072520404.jpg
Main Technical Specification
VOLTAGE RATINGS
Rated voltage(Ur)kV1.14
Rated short-time(1min)power-frequency withstand voltage(Ud)kV21
Rated lightning impulse withstand voltage(Peak)(Up)kV40
Rated frequency(fr)Hz50
CURRENT RATINGS
Rated current(Ir)A1250
Circuit resistance at lowest rated contact forceμΩ≤60
Rated short-time withstand current(lk)kA10
Rated duration of short-circuit(tk)s4
Rated peak withstand current(lp)kA10
Rated making currentkA6.3
Limit breaking currentA10
MECHANICAL DATA
Weight of movable partskg≤0.6
Closing force due to bellow and atmosphereN70±30
Force required to hold contacts open at full strokeN120±40
MECHANICAL REQUIREMENTS
Clearance between open contactsmm3±1
Average opening speed (average of first 75% contact gap)m/s0.4-0.5
Average closing speed (average of last 30% contact gap)m/s0.15-0.25
Rated added external contact final forceN250±50
Contact bouncing duration at closing operationms≤2
Closing and opening non-simultaneity of three-phase contactsms≤2
Maximum rebound during openingmm≤1
LIFE
Storage lifeyears20
Rated mechanical enduranceTimes300000
Contacts limit erosionmm3

Relevant information